Article ·
November 26, 2026
The attack on Poland's wind and solar farms shows why battery controllers need IEC 62443 certification
Andreas Werner

In December 2025, an attacker took at least 30 Polish wind and solar farms off their grid operators' screens, using default passwords and firmware that no device checked, Poland's national computer emergency response team reported. The controller inside a battery sits on the same kind of network, and IEC 62443, the standard Europe is adapting for its Cyber Resilience Act, is how a battery maker can now show that the controller is secured.
The attack in Poland began with a default password
On December 29, 2025, an attacker struck wind and solar farms across Poland, along with a manufacturer and a combined heat and power plant. CERT Polska, the country's national computer emergency response team, set out what happened in a report published a month later. At least 30 farms lost their communication link with the distribution system operator. They kept generating, and the transmission system operator saw no effect on grid stability, but the grid operators could no longer control the farms remotely.
How the attacker got in is the useful part for anyone who buys equipment with a controller in it. At most of the farms, the remote terminal units that link each site to its grid operator were still set up with their default login details, including an account called "Default". The attacker used that account to log in through each unit's web interface and load corrupted firmware, which left the units restarting in a loop. Newer firmware for the same units could check an update's digital signature before installing it, but the check stayed off unless the owner switched it on, and CERT Polska found it switched on nowhere. At farms using another make of controller, the attacker logged in with the factory administrator account and deleted the files the device needed to run.
A battery's controller is reached the same way
Every battery storage system is run by a battery management system, or BMS, which watches each cell and decides when the battery charges, discharges and shuts down to protect itself. The BMS reports to the site controller and often to a remote monitoring service, so it can be reached over a network just as the units in Poland were. BloombergNEF counted 112 gigawatts of new energy storage installed worldwide in 2025, which means the number of battery controllers on grids, industrial sites and data-center campuses is growing fast. Every one of them faces the same test as those Polish units: whether someone can log in with the factory password and load their own software.
What IEC 62443 asks of a controller
IEC 62443 is the series of standards that the International Electrotechnical Commission and the International Society of Automation wrote to secure industrial automation and control systems, and two of its parts apply to the maker of a piece of equipment. Part 4-1 looks at how the maker works: how it sets security requirements, designs and tests against them, deals with vulnerabilities once a product is in the field, and checks every update before it goes out. Part 4-2 looks at the component itself, against seven foundational requirements.
- Identification and authentication control. Every person and system proves who it is before the controller accepts a command, and the owner can change every password, including the ones set at the factory.
- Use control. Each user can do only what their role allows, and the controller records who changed what.
- System integrity. The controller can detect changes to its own software and checks that an update is genuine before installing it.
- Data confidentiality. Information such as passwords is protected where it is stored and while it travels.
- Restricted data flow. Traffic stays on the network paths it is meant to use.
- Timely response to events. Security events are logged in a form that can be reviewed.
- Resource availability. The controller keeps working under a flood of traffic and can be restored from a backup.
Both weaknesses in Poland fall within those seven requirements. A factory password nobody replaced is a failure of identification and authentication control, and a signature check that was available but switched off is a failure of system integrity. A Part 4-2 assessment examines whether a controller lets its owner change every factory password and whether it checks an update before installing it.
Security reviews are moving from claims of alignment to certificates
Some suppliers describe their equipment as aligned with IEC 62443, which is their own description and gives a reviewer nothing to check. A certificate is issued by an accredited certification body after it has assessed the product, and under the IECEE's international scheme for cyber security capability it names the standard, the product, the software version it covers and the body that issued it, so a reviewer can confirm it with that body.
The pressure to show that proof is arriving from several directions at once. Under the European Union's Cyber Resilience Act, manufacturers of products with digital elements have had to report actively exploited vulnerabilities since September 11, 2026, and the Act's main security obligations apply from December 11, 2027, according to the European Commission. CEN and CENELEC, the European standards bodies, are amending EN IEC 62443-4-1 and 4-2 so that they can serve as harmonized standards under the Act. Lithuania has gone further for power plants: its grid operators can now disconnect solar, wind and storage sites above 100 kilowatts that lack the cybersecurity measures its law requires, including multi-factor login and limits on remote access, pv magazine reported in June 2026. Data-center buyers are moving the same way, and NVIDIA's BESS Self-Qualification Guidelines, published in May 2026, point to IEC 62443, NERC CIP and the NIST Cybersecurity Framework for the security of a battery system's power conversion equipment.
For developers and owners, the consequence is that a security review now reaches the battery as well as the inverter and the site controller, and a certificate for the battery's own controller is the evidence that answers it most directly. Few batteries can offer one yet: most IEC 62443 certificates announced in energy storage so far cover inverters, power conversion systems or energy management software.
The owner still decides how secure a site is
A certificate describes what a controller can do, and the site owner still has to set it up securely. CERT Polska noted that one model of protection relay in the Polish attack would have disabled its default file-transfer account if it had been installed as its maker recommended, and the signature check on the remote terminal units was there all along. Owners and integrators still have to replace factory passwords, switch on the protections their equipment offers and keep control networks apart from the internet. IEC 62443 covers that work too, in Part 2-4 for the companies that integrate and maintain systems and Part 3-3 for the security of a complete system.
Where EnerVenue fits
On November 25, 2026, Victor Yan of UL Solutions presented the certificates at EnerVenue's factory in Changzhou. UL Solutions certified the Energy Rack's battery management system to IEC 62443-4-2, and EnerVenue's process for developing and updating that software to IEC 62443-4-1 at maturity level 2, which means the work follows documented, repeatable security procedures. The Energy Rack's battery management system also checks the digital signature of every firmware update before installing it, the safeguard that was switched off on the controllers in Poland. From its next software release in December, it will also make the installer change the factory password, which closes the other gap the attacker used.
"Cybersecurity now stands alongside physical safety as a basic capability that every energy storage system needs," said Jerry Peng, Head of Product Compliance and Safety at EnerVenue. "Our IEC 62443-4-1 and IEC 62443-4-2 certifications from UL Solutions show that cybersecurity is built into our work, from development through to delivery."
The Energy Rack is built on the Aqueous Metal Cell (AMC), which is certified to UL 1973 and has passed UL 9540A with no fire propagation. Security reviewers who need the certificates for an assessment can request them from our sales team, who will arrange a walk-through with the product engineers.
Sources
CERT Polska, "Energy Sector Incident Report: 29 December 2025", January 30, 2026.
BloombergNEF, "Energy storage enters the 100-gigawatt era: three things to know", May 7, 2026.
International Electrotechnical Commission, "IEC 62443", Systems Committee on Smart Energy.
European Commission, "Safer and more secure digital products", September 11, 2026.
CEN and CENELEC, "EN IEC 62443 to CRA", September 9, 2025.
NVIDIA, "BESS Self-Qualification Guidelines", version 1.0, May 28, 2026.
The energy landscape is changing fast. Stay ahead.
Join industry leaders who turn to our briefing for insights and analysis on storage technology, market shifts, and real-world deployments.
- Early access to industry research & whitepapers
- Market insights on energy storage trends
- Technology deep-dives from our engineering team
Related Articles
Born to Empower. Built to Endure.
Speak with an Advisor